Features

  • 30 sec adjustable purge time
  • 10 sec PTFI at treminal 5 and 6, 10 sec MTFI at terminal 5 and 15 sec MTFI at terminal 6, 4 sec Flame Failure Response Time(FFRT)
  • The programmer is compatible with both the ED500 and ED510 display modules

Standard Approvals

  • cULus Listed
  • FM Approved