Thos. Somerville Co.
Honeywell
Honeywell R7847A1033/U Solid State Plug-In Flame Amplifier
Honeywell

Honeywell R7847A1033/U Solid State Plug-In Flame Amplifier

BrandHoneywell
MFR Part NoR7847A1033/U
TSCO Part Number420312

Warranty Length

Limited

Features

  • Flame failures response time of 0.8 or 3 sec
  • Flame signal strength ranges from 0 to 5 VDC
  • Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation
  • Flame signal test jacks to measure amplifiers flame signal voltage
  • Dynamic self check amplifiers test the detectors and all electronic components in the flame detection system 7800 series relay module locks out on safety shutdown with flame detection system failures
  • Compatible with existing Honeywell® flame detectors
  • For use with C7004, C7005, C7007, C7008, C7009, Q179 rectifying flame rods and ultraviolet flame sensor C7012A, gas, oil, coal flame sensor
  • For 7800 series and R7140 relay module

Standard Approvals

  • CSA File No LR95329-3
  • Guide No MCCZ
  • UL File No MP268